Most test probes are round because most things that reach into an opening are round. Probe 14 is the exception. Its working end is a flat bar of roughly 3 mm by 1 mm, and that shape is the whole point: it models something a rod cannot — a thin, flat object pushed into a slot too narrow for a finger.

Why a bar and not a pin

A slot of 1 mm width rejects every round probe of practical size. But a piece of sheet metal, a thin blade, a folded strip of foil will enter it easily. Those objects are flat, and their passage through a slot depends on their thickness, not their width.

Probe 14 models exactly that. Its 1 mm thickness matches the sheet-like objects it represents; its 3 mm width gives it enough stiffness to be pushed without bending.

ProbeShapeObject modelled
124 mm rodsmall tool, pin
143 × 1 mm barsheet metal, blade, foil
170.5 mm pinwire, lead

Orientation is part of the test

Because the bar is flat, its orientation relative to the slot changes whether it enters. Presented edge-on to a slot of 1.2 mm, it enters; presented flat-on, it does not. Both orientations exist in the wording of the standard, and testing only one is testing half the hazard.

The practical rule: try both orientations at every slot, and record which ones admitted the probe. A result that says "not accessible" without stating the orientations attempted is not a result.

Where it is required

Probe 14 appears in product standards for equipment with narrow slots near live parts: ventilation arrays in a moulded case, seams between panels, the gap around a sliding switch, the slot in a socket that accepts a card or a blade.

It is not a general-purpose probe. Applying it everywhere produces findings the standard never asked about.

Two practical difficulties

Bending. A 1 mm thick bar is stiff along its width and flexible across its thickness. Pushing it into a tight slot can bow it, and a bowed bar presents a thinner profile and enters further than it should. Support it close to the entry, or use light force and watch for flex.

Edge condition. The 1 mm edges are what enter the slot, and they take the wear. A rounded edge presents a thicker profile at the entry, which makes the probe refuse a slot it used to enter — the safe direction, but it produces failures that do not exist. Check the edge with a straightedge or under magnification.

What the finding means

A probe 14 entry on a live part is a genuine and often serious finding, because the object it models is ordinary: a strip of metal, a piece of aluminium foil, a thin blade. Those are more likely to be present in a domestic or workshop environment than a 0.5 mm wire.

Record the location, the orientation that admitted the probe, and the depth reached. Those three items let someone else reproduce the finding, which is what turns an observation into evidence.